| Category | Feature |
| DC and TLC Areas | | Capacity | Over 800 servers and 4000 TB of storage. |
|
| IT Infrastructure | | Reliability | High reliability is achieved through virtualization, clustering, and fault tolerance technologies. |
|
| Scalability | Similarly, scalability is ensured through virtualization and load balancing technologies. |
|
| Data Integrity | The use of Storage Area Network (SAN) in highly redundant configurations fully supports the integrity of stored data. |
|
| Security | LAN/WAN security is implemented via VLANs, Access Lists, Access Maps, and firewall rules. |
|
| Internal LAN | The internal cabling in the Data Center is category 6A, allowing LAN transmission speeds of up to 10Gbps. |
|
| Network Equipment | CISCO switches and routers; CISCO and freeBSD firewalls. |
|
| Connectivity | | Interconnections | Fastweb via fiber optics; Telecom NWS via fiber optics. |
|
|
| Round Trip Delay | Round trip delay < 10 ms. |
|
| Network Availability | 99,95% |
|
| Technology | SDH and DWDM technology with redundant circuits routed through different paths to ensure high service reliability. |
|
| Autonomous System | AS 200761 |
|
| Physical Security | | On-Site Supervision | All services are constantly monitored by Monitoring and Intrusion Detection Systems, as well as supervised by internal personnel. |
|
| Armoring | Armored doors, shatterproof glass, road bollards, and reinforced concrete planters. |
|
| Smoke Detection & Evacuation | The system complies with UNI 9795 and is certified UNI12094, EN54-2, EN54-4 for smoke detection and alert. It uses analog dual-technology point-type thermovelocimetric smoke detectors. Indicator panels are installed. |
|
| Fire Extinguishing System | The extinguishing system, compliant with UNI 9795 and certified UNI12094, EN54-2, EN54-4, uses aerosol technology. |
|
| Intrusion Detection System | The system consists of volumetric sensors within the rooms, perimeter sensors on external walls, and anti-burglary sensors on access doors. All sensors are connected to a management control unit, fully controllable via software connected to a dedicated VLAN. |
|
| Access Control System | The access control system is designed to allow entry to authorized personnel only and to retain the access history over time. Access is granted via badge and fingerprint recognition. Detector signals are relayed to a local computer, enabling real-time status monitoring both locally and remotely. |
|
| Video Surveillance | The internal and external video surveillance system is fully digital. Supervision can be performed locally or remotely in real time. |
|
| Power supply | | Electrical System | L'impianto elettrico è stato progettato e realizzato secondo criteri di modularità e di ampliamento del servizio, nonchè di semplicità di manutenzione. Sono state installate linee separate per la gestione dell'UPS, dei singoli chiller e dell'alimentazione di servizio. |
|
| UPS | The installed UPS is a high-efficiency three-phase model with integrated modular distribution, scalable according to power requirements, and aligned with the growth of the Data Center's demand. Every device in the Data Center is powered by protected electricity provided by the UPS. |
|
| Generator | The generator is equipped with an automatic transfer unit and is sized to allow full operation for up to 16 hours. |
|
| Cooling | | Air Conditioning | The cooling system operates in InRow mode. Thus, temperature is dynamically modulated according to the cooling needs of each individual module within the rack cabinets. |
|
| Energy Saving | Thanks to the designed cooling architecture, energy savings of up to 40% are achieved. |
|
| Building Architecture | | Static Load Capacity | The building’s floor has a static load capacity of 2.0 tons/sqm. |
|
| Raised Floor | The raised floor consists of modular 60 cm x 60 cm panels with a minimum fire resistance of REI 60, 4 cm thickness, 2200 Kg/sqm load capacity, removable panels via suction cup, and an anti-static, wear-resistant surface. The support surface is coated with anti-static paint to prevent harmful dust propagation. The metal support structure is made of adjustable galvanized steel feet. The flooring is completed with an anti-static baseboard. |
|
| Wall Finishes | Interior surfaces are finished with cement mortar plaster and painted white. |
|
| Fixtures and Windows | Glazing ensures shatter resistance (anti-break coefficient: 6x from outside, 5x from inside) and protection against intrusion. Anti-intrusion security is also provided by specific security systems, bollards, and reinforced concrete planters. The Data Center entrance door is armored. |
|
| Fireproofing Provisions | Data Center rooms ensure a minimum fire resistance of REI 60 - REI 180. |
|